12V Battery Bank Calculator

Size an off-grid battery bank in amp-hours and kWh, with the batteries and solar array to match.

Loads the state's average price per watt, electricity price and solar output. You can edit any of them.
kWh
days
Lithium iron phosphate often 80–100%; lead-acid 50%.
%
More settings
%
Ah
From NREL PVWatts for your state.
kWh/kW

Your result

Enter your numbers and press the button. Your result appears here.

At 12 V, every kWh of storage is 83.3 Ah. 12 V suits vans, cabins and small loads.

How it works

Ah = daily kWh × days × 1,000 ÷ (volts × depth of discharge × efficiency). Batteries in series = system volts ÷ battery volts.

Example: 2 kWh a day for 2 days at 12 V and 80% depth of discharge needs 463 Ah (5.6 kWh).

At a glance

Same settings as the calculator, changing only the daily use.

Daily useBankNominalSolar array
0.5 kWh116 Ah at 12 V1.4 kWh0.13 kW
1 kWh231 Ah at 12 V2.8 kWh0.27 kW
2 kWh463 Ah at 12 V5.6 kWh0.53 kW
3 kWh694 Ah at 12 V8.3 kWh0.80 kW
4 kWh926 Ah at 12 V11.1 kWh1.07 kW

Common questions

What voltage should an off-grid system use?

12 V for small loads, 24 V for mid-size systems and 48 V for whole homes. Higher voltage means lower current and thinner cables.

How many days of storage do I need?

Two to three days is common where cloudy spells are short. A backup generator lets you use fewer.